F-03 · Commissioning record missing VAV functional test sheet

Riverside Office HVAC (CS-PILOT-0142) · requirement R-05 · Commissioning record presence

Issue identifiedAutomated check — source verifiedmedium priority

What this means

The commissioning record contains air-handling functional tests. No functional performance test sheet for the VAV terminal zones appears in the supplied files.

Original stored explanation retained; no safe automatic simplification is available.

What would resolve it

Supply evidence addressing the stated requirement: Commissioning record shall include functional performance test results for air handling, terminal and control systems.

Your review

Automated source checks verified this finding. No individual approval is needed. This is not a human confirmation or project acceptance.

Sample only. Changes are temporary; Reset demo restores the sample. No customer request is submitted.

How this finding was routed

The commissioning record contents page lists test sheets explicitly, so the absent VAV sheet is established by the cited source.

Checked against the cited sources by the automated comparison. No person has reviewed it, so it must not be described as human-confirmed.

Evidence

Project requirement on the left, supplied source excerpts on the right. Panels stack on small screens.

Project requirement

Project Specification 23 08 00page 4
Commissioning record shall include functional performance test results for air handling, terminal and control systems.

Supplied files

Cx Record.pdfpage 2
Contents: FPT-01 Rooftop units · FPT-02 Exhaust fans · FPT-04 Smoke control interface.

Proposed next action

Request the VAV zone functional performance test sheets from the commissioning provider.

Reviewer decision

Use the sample actions to preview each reviewer outcome.

Internal sample note. It is not shown in the customer preview.

Appears in the demo audit history.

No owner approval needed. Checked against the cited sources by the automated comparison; it publishes without a reviewer decision. This is not a human confirmation.